Specification
Parameter | |
Measurement range | Humidity: 0~100%RH |
Temperature: -40~200℃(customizable) | |
Accuracy at 25℃ | Humidity: ±2%RH (20~80%RH) |
Temperature: ±0.2℃ | |
Repeatability | Humidity: ±0.2%RH |
Temperature: ±0.1℃ | |
Response time | Humidity: ≤15s |
Temperature: 30S | |
Outputs | Analog signal 4-20mA and Digital interface RS485 |
Power supply | 24V DC |
Current consumption | Max 80mA |
Transmitter working temperature | -40~70℃ |
Electrical connection | Terminal block |
Installation methods | Duct mounted by Thread/Flange/Clamp; |
Wall mounted with an extra probe | |
Pressure resistance | Max. 6bar |
Material | Housing: Cast Aluminium Stem: 304 Probe:316L |
Dimension | |
Duct mounted | Wall mounted |
![]() Stem length: 400mm standard, upto 800mm | ![]() Cable length: 1m standard, upto 3m. Probe: 150mm standard, 52mm and 87mm options. |